IMPORTANT: Connecting the Pump Start Relay should only be done by a licensed electrician following local codes. Improper installation could result in shock or fire hazard.
| Wire | Connection | |
|---|---|---|
| Black | Hot Wire | A single wire using for a 120 VAC connection. |
| Black | Hot Wire | A second wire is used for a 240 VAC connection. |
| Blue | Neutral Wire | Neutral wire passed through the terminal connector block. |
| Green | Ground wire | Ground wire passed through the terminal connector block. |
| Yellow | Controller Common Wire | Connect the yellow wire to the C (Common) terminal inside the controller. |
| Yellow | Controller P/MV Wire | Connect the remaining yellow wire from the pump start relay to the P/MV (Pump) terminal. |
- To prevent electric shock, turn the main circuit breaker switch to “off” before making any electrical connections.
- Assemble conduit piping and connect AC power from the power source to one side (LINE IN) of the relay.
- Assemble conduit piping and connect wiring from the pump motor to the other side of the relay (LOAD OUT).
- Check to make sure there are no exposed or loose connections.